Product Code: KE-DM3110YS02
Call ButtonAdresli

KE-DM3110YS02, a yellow (RAL 1003) manual call point used in Kidde Excellence series addressable fire alarm systems. Single action design: pressing the glass element transmits the alarm directly to the control panel. French language version for the France market. The text on the glass reads "DÉCLENCHEUR MANUEL SYSTÈME D'EXTINCTION". The housing contains a short-circuit isolator; when a short circuit occurs at one point in the loop, the remainder of the line continues to operate, preventing the entire floor from going dark due to a single fault. Dual-color LED indicator reads alarm, isolated, fault, and communication status at 180° viewing angle in place. Comes with reusable glass element, test connector, and test key — functional testing can be performed without breaking the glass, eliminating replacement costs at each test. Operating voltage 17–38 VDC, operating temperature −25…+72°C, protection class IP41.

Technical specifications

ArchitectureAdresli
IP RatingIP41