Fire system maintenance across Türkiye0312 385 15 66
Products / Fire Detection Systems / Asenware / Asenware AW-D127 Addressable Fan Control Module
Fire Detection SystemsEarly detection, safe evacuationAll products →
Asenware

Asenware AW-D127 Addressable Fan Control Module

Product Code: AW-D127
Module & IsolatorAdresli

AW-D127 is a control module addressed to the fire alarm loop that activates a fan or motorized damper actuator at alarm time. The control side switches AC 220 V or DC 24 V loads; the monitoring side is powered from the loop at 24 V, alarm current on the loop does not exceed 40 mA, and on the control side does not exceed 500 mA. The module not only sends commands but also feeds back the actuator's angular position to the panel according to <5° (closed) and >85° (open) thresholds; it also detects open circuit condition in the actuator motor. It is not a speed or frequency control unit; its function is to drive the damper/gate position in a verifiable manner and convey the status to the center. It works with AW-FP200 and AW-FP128 addressable panels and with conventional systems; it is designed for operation between -10°C and +50°C, at %5-95 humidity without condensation, and for indoor mounting only.

Technical specifications

ArchitectureAdresli