Fire system maintenance across Türkiye0312 385 15 66
Products / Fire Detection Systems / Asenware / Asenware AW-CSD311 Quick-Response Conventional Smoke Detector
Fire Detection SystemsEarly detection, safe evacuationAll products →
Asenware AW-CSD311 Quick-Response Conventional Smoke Detector
Asenware

Asenware AW-CSD311 Quick-Response Conventional Smoke Detector

Product Code: AW-CSD311
Smoke DetectorKonvansiyonel

AW-CSD311 is an optical-principle smoke detector connected to conventional fire detection loops; it alarms by measuring light scattering caused by smoke particles entering the sensing chamber. Supply range is 9-28 VDC and since it operates independently of polarity, reversed wiring of loop terminals does not produce a fault during commissioning — in multi-story buildings where numerous detectors are installed in a short time, this detail saves time in the field. In alarm condition, the current drawn does not exceed 15 mA at 24 VDC; this is the value that must be considered along with panel output capacity when calculating how many detectors can be connected to one zone loop. The product detects smoke only and has no heat-sensing function; in spaces where temperature rise occurs before smoke, a heat detector must be positioned separately during the design phase.

Technical specifications

ArchitectureKonvansiyonel
Operating Voltage9-28 VDC, polarity independent
Alarm Current≤15 mA @24 VDC